EXE HVJB (15KV) 

Based on the HVJB range but suitable for up to 15kV, the ABJB can accept up to 4 phase connections either straight through or bottom entry only. The unit can accommodate up to three connectors per phase.

Enclosure Ratings

Product Reference*

Width

(mm)

Height

(MM)

Depth

(MM)

Maximum Power Rating (W)

Maximum Voltage (kV)

Maximum Current (A)

Maximum Conductor Size (mm2)

Maximum Ways

Weight (kg)

Standard Specifications

Enclosure Type

Ingress Protection

Impact Resistance

Material

 

 Ambient Temp Rating

Maximum Terminations

No. of Gland Plates

 Crimp lugs

 Earthing

 Mounting

 

Certification

Area Classification

Type of Protection

Apparatus Coding

 Certificate Number

High Voltage

IP66 to EN60529, Type 4X, DTS-01

>7Nm

2mm 316L Stainless Steel (EN 1.4404) enclosure with orbital finish, silicone gasket and captive 316 stainless steel fasteners, 3mm 316L (EN 1.4404) Stainless Steel gland plates

 -20°C to +40°C or -50°C to +55°C (refer to certificate)

3 conductors per phase in & 3 conductors per phase out

Dependant upon configuration 

16mm2 to 1000mm2

Via studs on enclosure, door and gland plates

Via 3mm thick external mounting straps, slotted upper strap for ease of installation Certification

Enter your text here

 Zone 1 & 21, Gas and Dust / Class 1 Div 2

Ex sb (Apparatus Certified), Ex tb (Dust Protected)

Ex sb IIC 2 GD T4 Gb, Ex tb IIIC T70°C /T80°C Db

CML16ATEX7322X, IECEx CML 16.0099X

X

X(M)

Y

Y(M)

Z

  • Fault rated 45kA for 0.2 seconds.
  • DTS-01 deluge tested enclosure.
  • Wide ambient temp range.
  • Heavy-duty machined hinges with lift-off cover pad-lockable cover.

ABJB-73(x-x)

650

950

300

259

15

980

1000

3

75

ABJB-83(x-x)

800

1250

300

346

15

980

1000

3

102

ABJB-84(x-x)

800

1250

300

346

15

980

1000

4

102

Dimensions

ABJB73

ABJB83

ABJB84

650

700

950

750

300

800

850

1250

1050

300

800

850

1250

1050

300

Dimensions in mm

Options

ACH

EP

PS

PT

BPG

CP

MB

Anti-condensation heater (dependent upon available internal dimensions)

Electro-polished

Epoxy powder coated, smooth finish (RAL colour may be specified)

Epoxy powder coated, Hammer Grey

Single core terminal box mounted internally

Internal access protection cover plate

1 Mounting boss for lifting eye bolts

Add the required suffix to the product reference.

Example: ABJB73(2-2)PT = ABJB7 with 2 x conductors per phase top entry and 2 x conductor per phase bottom entry, Hammer paint finish.

Accessories

ABDM2010SS

ABDM2510SS

FBM12EEMS***

FBM16EEMS***

M20 Breather drain

M25 Breather drain

 M12 Lifting Eye bolts in mild steel, Note: Requires MB suffix option listed above

M16 Lifting Eye bolts in mild steel, Note: Requires MB suffix option listed above

***Stainless steel lifting eye bolts also available, contact sales for information

Product Reference*

Width

(mm)

Height

(MM)

 

Depth

(MM)

 

Maximum Power Rating

(W)

Maximum Voltage (kV)

Maximum Current (A)

Maximum Conductor Size (mm2)

Maximum Ways

Weight (kg)

High Voltage

IP66 to EN60529, Type 4X, DTS-01

>7Nm

2mm 316L Stainless Steel (EN 1.4404) enclosure with orbital finish, silicone gasket and captive 316 stainless steel fasteners, 3mm 316L (EN 1.4404) Stainless Steel gland plates

 -20°C to +40°C or -50°C to +55°C (refer to certificate)

3 conductors per phase in & 3 conductors per phase out

Dependant upon configuration 

16mm2 to 1000mm2

Via studs on enclosure, door and gland plates

Via 3mm thick external mounting straps, slotted upper strap for ease of installation Certification

Enter your text here

 Zone 1 & 21, Gas and Dust / Class 1 Div 2

Ex sb (Apparatus Certified), Ex tb (Dust Protected)

Ex sb IIC 2 GD T4 Gb, Ex tb IIIC T70°C /T80°C Db

CML16ATEX7322X, IECEx CML 16.0099X

Enclosure Type

Ingress Protection

Impact Resistance

Material

 

 

 Ambient Temp Rating

Maximum Terminations

No. of Gland Plates

 Crimp lugs

 Earthing

 Mounting

 

Certification

Area Classification

Type of Protection

Apparatus Coding

 Certificate Number